400 IBM BladeCenter JS23 and JS43 Implementation Guide
Figure 10-2 Additional power settings
Figure 10-3 Chassis thermal and trending options
Selecting the Power Management Policy link (number 1 as shown above) will
allow the user to select three different management policies. Figure 10-4 on
page 401 shows and example of this option.
There are three different selections that can be applied to manage the power
domain. As mentioned above, in the BCH there are two power domains. Each
domain can set this policy separately and they do not need to match.
The Basic Power Management option is the least conservative of the three
available options. This policy does not guarantee redundancy so if a power
module fails, the BladeCenter chassis could be affected. When this policy is in
effect the value for Maximum Total Power Limit is used to determine if a blade
can power on. As long as the power used is below this maximum value the blade
can continue the power on procedure. If one of the power modules fail, blades
capable of throttling may be throttled back to keep the domain usage below the
maximum limit. If the limit is reached, the domain may be affected by power loss.